Voltage Drop Calculator

5.0

Your Voltage Drop

Voltage Drop

1.03%

Within 3% (good)

Voltage Drop

2.47 V

across the run

End Voltage

237.53 V

at the load

Conductor

Copper 4 AWG

41,740 circular mils

NEC Recommendation

PASS

≤3% branch / ≤5% total

Estimate only. NEC 210.19 / 215.2 informational notes recommend ≤3% on a branch circuit and ≤5% total (feeder + branch). This is a one-way DC/AC resistance estimate using the circular-mils method and does not account for power factor, conductor temperature, or conduit type. Verify against the NEC and your AHJ; it does not replace a licensed design.

Circuit

Nominal source voltage, e.g. 120, 240, 208, 480.

Phase

Conductor

Material
Wire size

Load & Distance

Load current in amps

Length of the run, one direction

Quote the job in minutes

Sized the conductors? Turn the work into a professional estimate. Invoicer helps electricians create and send estimates and invoices and get paid faster.

Try Free

How to Calculate Voltage Drop

1

Enter your circuit

Set the system voltage and pick single phase or three phase. The phase changes the multiplier in the voltage drop formula.

2

Choose the conductor

Select copper or aluminum and the wire size. Aluminum has higher resistance, so the same run drops more voltage than copper.

3

Add load & distance

Enter the load current in amps and the one-way length of the run in feet. Longer runs and higher current both increase the drop.

4

Check against the NEC

Read the percent drop and compare it to the NEC's 3% branch / 5% total recommendation. If it's too high, upsize the wire and recalculate.

Who Uses This Tool

Electricians

Size conductors for long runs and confirm a circuit stays within NEC voltage drop limits before pulling wire.

Solar & Battery Installers

Keep DC and AC voltage drop in spec across panel strings, inverters, and battery runs to protect system performance.

Low-Voltage & AV Techs

Check long control, power, and speaker runs so the device at the far end still gets enough voltage to work reliably.

Frequently Asked Questions

How do you calculate voltage drop?
This calculator uses the circular-mils method: voltage drop = (phase factor × K × current × distance) ÷ circular mils. K is the resistivity of the conductor (12.9 for copper, 21.2 for aluminum, in ohm-circular-mils per foot), the phase factor is 2 for single phase and 1.732 for three phase, current is in amps, and distance is the one-way length in feet. Divide the result by your system voltage to get the percent drop.
What is the NEC limit for voltage drop?
The NEC does not hard-limit voltage drop in its main rules, but informational notes to 210.19 (branch circuits) and 215.2 (feeders) recommend a maximum of 3% on a branch circuit and 5% total across the feeder and branch combined. These are recommendations for reasonable efficiency, not enforceable code, though your AHJ or project spec may require them.
Is 3% or 5% the limit I should design to?
Aim for 3% or less on the branch circuit that feeds the load, and keep the feeder plus branch combined at 5% or less. Designing to 3% gives you headroom and better efficiency. If a single long run pushes you past 3%, upsizing the conductor one or two sizes usually brings it back into range.
Why does aluminum drop more voltage than copper?
Aluminum has higher electrical resistance than copper, so for the same wire size and run it drops more voltage. That is why aluminum conductors are typically sized one or two AWG larger than copper to carry the same load. This calculator uses K = 12.9 for copper and K = 21.2 for aluminum to reflect that difference.
Do I enter one-way or round-trip distance?
Enter the one-way distance — the length of the run in a single direction. The calculator already accounts for current traveling out and back through the phase factor (2 for single phase, 1.732 for three phase), so you should not double the distance yourself.
Does this account for power factor and temperature?
No. This is a DC/AC resistance estimate using the circular-mils method. It does not adjust for power factor, conductor operating temperature, or conduit type, all of which can affect real-world drop. For motor loads, long runs, or critical circuits, verify with the conductor's published AC resistance and reactance values and the NEC.
How do I fix a voltage drop that's too high?
The most common fix is to upsize the conductor — a larger wire has more circular mils and less resistance, which lowers the drop. You can also shorten the run, reduce the load, or raise the system voltage where the design allows. Re-run the calculation after each change until you are within the 3% / 5% target.
Why does three phase drop less voltage than single phase?
In a balanced three-phase circuit the current returns through the other phase conductors rather than a dedicated neutral, so the effective resistive path is shorter. That is reflected in the phase factor — 1.732 (the square root of 3) for three phase versus 2 for single phase. For the same wire, current, and distance, a three-phase run shows a lower voltage drop.
Is this calculator free and is my data saved?
Yes, the calculator is completely free with no signup required. Your inputs are saved locally in your browser so they persist between visits — nothing is uploaded to a server. Clearing your browser data will erase your saved values.