Wire Size & Ampacity Calculator
Recommended Wire Size
Recommended Wire
8 AWG
copper, 75°C column
Required
50.0 A
load current
Wire Rated
50 A
ampacity
Temp Column
75°C
insulation temperature rating
Base ampacity only. Values come from NEC Table 310.16 (copper). This does not apply ambient-temperature or conduit-fill (more-than-3-conductors) derating per 310.15, voltage-drop sizing, or the 60°C termination rule for small breakers. Verify with the NEC and your AHJ — this does not replace a licensed design.
Load Current
The load or breaker rating in amps the conductor must carry.
Insulation Temperature Rating
Use the column your conductor insulation and terminations are rated for. THHN/THWN-2 is 90°C, but terminations are often only rated 75°C.
Continuous Load
Quote the work in minutes
Sized the run? Turn the job into a professional estimate. Invoicer helps electricians and installers send polished estimates and invoices and get paid faster.
Try FreeHow to Size a Wire by Ampacity
Enter the load current
Type in the load or breaker rating in amps that the conductor needs to carry.
Pick the temperature column
Choose 60°C, 75°C, or 90°C to match your conductor insulation and the lowest-rated termination on the circuit.
Flag continuous loads
Toggle the continuous-load option for anything running 3 hours or more, and the tool sizes at 125% of the current.
Read the recommended gauge
The tool returns the smallest copper conductor that meets the required ampacity. Copy it into your records or a quote.
Who Uses This Tool
Electricians
Size conductors fast on the truck without flipping through the code book for every circuit.
Solar & EV Installers
Size feeders and branch circuits for PV strings, inverters, and EV chargers with the continuous-load factor built in.
Maintenance & Facilities Techs
Verify that existing wiring is rated for a load before adding equipment or changing a breaker.